A Static Var Generator continuously monitors system voltage and current via external current transformers. Its digital controller calculates the magnitude and direction of reactive current demanded by the load.
The operation consists of four key steps:
1. Current Detection: Current transformers capture load current in real time.
2. Reactive Power Calculation: The controller determines if inductive or capacitive compensation is needed.
3. Current Generation: The IGBT converter produces the required compensation current.
4. Grid Compensation: Compensation current is injected into the power system to align the phase of load current with voltage.
If the load draws inductive reactive power, the SVG supplies capacitive current. If the load generates capacitive reactive power, the SVG absorbs it. This bidirectional operation maintains steady power factor correction amid fluctuating loads.

Static Var Generators have multiple advantages over conventional reactive power compensation equipment such as capacitor banks and reactors:
Fast Response: SVGs react rapidly to power system variations, ideal for compensating dynamic loads and grid disturbances.
Continuous Control: SVGs deliver stepless reactive power regulation for precise tuning and better power quality. When the load draws inductive or capacitive current, the load current lags or leads the voltage. The SVG detects the phase difference and injects leading or lagging compensation current into the grid. This aligns the current phase with the voltage on the transformer side, bringing the fundamental power factor close to unity.
Voltage Stability: SVGs regulate voltage by sourcing or sinking reactive power to avoid voltage fluctuations and unbalanced loads, sustaining stable system operation. They provide instant stepless reactive compensation to resolve power quality issues from non-linear and fast-changing loads including VFDs, cranes, welding machines, rolling mills, and equipment used in chemical, cement, sugar and textile plants.
Harmonic Filtration: SVGs can be fitted with extra filters to suppress harmonics and improve overall power quality. Hybrid solutions combining SVG and thyristor-switched filter banks are available as a cost-effective option. They eliminate harmonic currents and voltages, correct both lagging and leading power factor, reduce voltage sags and swells, mitigate flicker and balance three-phase loads.
Compact Structure: SVGs occupy much less floor space than traditional compensation solutions, which makes them perfect for sites with limited installation space.