Surge in PV Reverse Voltage | Why Are Traditional Capacitor Cabinets Becoming Less Effective?
In the second month after a commercial and industrial rooftop solar system was connected to the grid, the owner noticed that the monthly power factor correction charges had risen rather than fallen, and the power factor on the performance report showed an “inverted” anomaly. In another case, a low-voltage capacitor compensation cabinet that had been in operation for many years began exhibiting issues after the PV system went online: the contactor repeatedly tripped and reset at noon, the capacitors bulged, and fuses blew for no apparent reason. Although the controller displayed a normal power factor, the capacitors were clearly failing. The problem did not lie with the inverter, but rather with the compensation cabinet’s control logic and primary wiring—it simply wasn’t designed to handle “reverse power flow.”

Line voltage drop is approximately ΔU ≈ (P · R + Q · X) / U_N. Under load conditions, P and Q are positive and in the same direction, causing the terminal voltage to drop; the distribution transformer tap setting is determined based on the principle that “the terminal voltage should not be too low under heavy load.” After PV integration, at noon, P reverses direction at the grid-connection point, causing power to be fed back into the grid; ΔU becomes negative, and the terminal voltage is raised. According to GB/T 12325, the voltage deviation for three-phase systems at 20 kV and below is ±7%, meaning the upper limit for 380 V is approximately 407 V. The first to experience a voltage surge are always the few households at the end of the transformer service area.
The logic behind capacitor switching cabinets is “engage capacitors when the power factor is low,” which results in only reactive power being generated; however, during the day when solar power generation is high, the distribution substation needs to absorb reactive power and bring the voltage back within the limit. Engaging capacitors at this point is like adding fuel to the fire: it leads to higher voltage, reverse reactive power flow, and an inverted power factor, turning the power factor adjustment fee from a reward into a penalty. Traditional controllers do not account for power direction in their decision-making criteria. The system must operate in all four quadrants: inductive absorption during the day and capacitive injection at night. This is precisely why SVGs are essential in PV service areas.
Although the total current distortion ratio of the inverter is required to be kept within 5%, the compensation capacitors and system inductance form a parallel resonant circuit. Once a certain harmonic is amplified, the capacitors become overloaded and the fuses trip, the total voltage distortion limits specified in GB/T 14549 (0.38 kV: 5%; 10 kV: 4%; 35 kV and above: 3%) are also exceeded. Therefore, capacitors cannot be directly connected to the compensation branch; a tuned thermal reactor must be connected in series: according to n = 1/√k, a 7% reactance rate tunes to approximately 189 Hz, ensuring that harmonics of the 5th order and higher encounter the reactor rather than the capacitor; in cases where the 3rd-order harmonic is high, a 14% reactance rate is used, tuning the frequency down to approximately 134 Hz. Selecting the wrong reactance rate turns the compensation cabinet into a platform for harmonics.
Furthermore, when single-phase inverters are connected phase-by-phase, the following phenomena occur at midday: “one phase has the highest reverse power flow, the highest voltage on that phase, and a reverse increase in neutral current.” According to GB/T 15543, the unbalance limit is 2% (4% for short-term conditions), and these limits are easily exceeded at the end of the distribution area.
I. Relying on the inverter’s own reactive power, with no additional equipment required
GB/T 33592—2026, “Control Specifications for Grid-Connected Operation of Distributed Power Sources,” which took effect on February 1, 2027, revises item by item the start-up and shutdown, active power, primary frequency regulation, reactive power and voltage, fault ride-through, communication, and automation of distributed power sources at 35 kV and below, and establishes corresponding test methods. However, since the apparent power of an inverter remains constant, voltage regulation margins are limited during full-load operation in daylight hours; even if a single unit is capable, it does not necessarily mean that the entire service area can operate in a coordinated manner.
II. Substation-Level Coordination Between Main and Distribution Transformers
In 2026, State Grid Xuzhou implemented a “risk control matrix” that monitors low-voltage PV output every 5 minutes. By optimizing distribution transformer tap settings and adding dynamic reactive power compensation at the substation end, it replaces simple output restrictions with flexible regulation. According to public reports, this approach improved PV utilization efficiency by 25.3%. While this addresses the root cause, it requires cooperation from the power supply side.
III. Four-Quadrant SVG and APF
Suitable for scenarios where inverters cannot provide sufficient reserve capacity but must first pass acceptance testing, these solutions offer millisecond-level response times and simultaneously resolve voltage, reverse power flow, harmonics, and unbalance issues. The trade-off involves investment, power losses, and O&M costs.
The growth opportunity lies not in selling a few more cabinets, but in shifting from selling individual devices to selling grid-connection solutions—including bidirectional power factor control with power direction criteria, reactor selection based on measured spectra along with resonance verification calculations, and a policy interface that integrates with smart terminals in transformer districts.
Voltage sampling is performed on the controlled busbar, while current sampling (CT) remains installed downstream of the junction point between the load branch and the compensation branch; it must not be installed on the utility-side feeder, otherwise, during reverse power flow, the device will include its own output in the load reactive power. For capacitive controllers, the standard wiring method is to connect to the main feeder; do not mix these two sets of rules. If the harmonic background is not measured, do not report the compensation capacity; if the system cannot identify a “need for reactive power absorption,” it is better not to install it at all.
To owners and EPC contractors: Before grid connection, record a voltage curve at the grid connection point from 11:00 to 14:00; do not limit measurements to nighttime only. In the technical agreement, specify the reactive power absorption capacity (kvar), rather than simply stating “compensation capacity 300 kvar.”
As of the end of July 2026, the nation’s installed photovoltaic capacity stood at 1.286 billion kilowatts, accounting for 31.5% of total installed power generation capacity—exceeding the 1.285 billion kilowatts of coal-fired power. Distributed PV installations surpassed 8.3 million households, with 72.07 GW added in the first half of the year. The first half of the race focused on cost per watt; the second half will focus on how much PV capacity a distribution transformer can support per kilovolt-ampere.
If the power supply office asked you tomorrow to provide the “daytime voltage curve at the grid connection point” and “proof of reactive power absorption capacity,” would that old control cabinet on-site—which only knows how to switch on capacitors—be able to provide the answers?